When the first cold snap arrives, no-heat calls flood in. The fastest technicians are not the ones who guess well; they follow the same sequence every time, letting the furnace’s own operating sequence tell them where it stops. This guide covers a standard diagnostic order for a modern gas furnace with an inducer motor and hot surface ignition. Always follow the manufacturer’s instructions for the model in front of you.
Start with the customer and the thermostat
- Ask what happened: no heat at all, heat that starts and stops, or heat that is weak.
- Check the thermostat mode, set point, schedule and batteries.
- Confirm the thermostat is actually calling. With the call on, you should be able to measure 24 volts between W and C at the furnace control board. Our thermostat wiring guide explains the terminals.
A surprising share of no-heat calls end here: a thermostat in the wrong mode, dead batteries, or a schedule nobody remembers setting.
Check power and switches
- Service switch on, and the breaker not tripped.
- Door safety switch closed with the panel in place.
- 120 volts at the board and 24 volts from the transformer.
- The fuse on the control board intact.
A blown low-voltage fuse usually means a short somewhere in the 24-volt wiring. Find the short before replacing the fuse. See how to use a multimeter.
Read the error code
Most modern furnaces flash a diagnostic code on an LED on the control board. Before you reset anything, count the flashes and look up the code on the label inside the panel door. A reset clears stored codes on many boards, so read and record the code first.
Follow the sequence of operation
A typical gas furnace with hot surface ignition runs through the same steps every time it starts. Watch which step fails.

| Where it stops | Common causes to check |
|---|---|
| Inducer does not start | No call reaching the board, failed inducer motor or capacitor, failed board relay |
| Inducer runs, no ignition | Pressure switch not closing: blocked vent or intake, cracked or water-filled hose, blocked condensate trap, failed switch |
| Igniter does not glow | Open igniter, loose connection, no voltage from the board |
| Igniter glows, no flame | Gas supply off, failed gas valve or no voltage to it, incorrect gas pressure |
| Lights then shuts off in seconds | Weak flame signal: dirty sensor, poor ground, flame not touching the rod |
| Runs, then cycles off on limit | Restricted airflow: dirty filter, closed registers, dirty blower or coil, high static pressure |
Pressure switch problems
On condensing furnaces, a blocked condensate trap or drain is one of the most common reasons the pressure switch will not close. Water backs up into the inducer housing or the pressure switch hose. Check the trap and drain before condemning the switch. See condensate drain problems.
Flame sensing
If the burners light and then go out after a few seconds, the control board is not seeing a flame signal. Clean the flame sensor with a light abrasive pad, check that the burner flame envelops the rod, and check the ground connection. Measure the flame signal in DC microamps and compare it with the manufacturer’s minimum.
Limit trips
A furnace that heats for a while and then shuts down, with the blower still running, is often tripping its high limit because of poor airflow. Check the filter, the blower wheel, the evaporator coil above the furnace, and total external static pressure. Measure temperature rise against the nameplate range. Never jump out a limit or rollout switch to keep a furnace running.
Rollout switch tripped
A tripped flame rollout switch means flame came out of the burner area. That is a serious warning sign. Look for a blocked heat exchanger or vent, incorrect gas pressure or a cracked heat exchanger before resetting it, and do not leave the furnace running if you find an unsafe condition. Carry a carbon monoxide monitor on every heating call; see carbon monoxide safety.
Before you leave
- Run the furnace through several complete cycles.
- Record the error code you found, the readings you took and the parts replaced.
- Explain the cause to the customer, and recommend maintenance if dirt or neglect caused the failure.
For the maintenance side, see the furnace tune-up checklist. For documenting the call, see how to document a service call.
Related guides
Sources
- U.S. Consumer Product Safety Commission: Carbon monoxide information center
- ENERGY STAR: Heating and cooling maintenance checklist
Six everyday forms in Word and PDF, plus Excel workbooks that total mileage reimbursement and overtime pay.
Not sure yet? Try two forms free or see all packs.
Frequently asked questions
Why does my furnace light and then shut off after a few seconds?
The most common cause is a weak flame signal, often from a dirty flame sensor, a poor ground or a flame that does not touch the sensor rod. The control board shuts the gas off if it cannot prove flame.
What does it mean when the inducer runs but the furnace does not light?
The control board is usually waiting for the pressure switch to close. Check for a blocked vent or intake, a damaged or water-filled hose, a blocked condensate trap or a failed switch.
Should I reset a tripped rollout switch?
Not until you have found out why it tripped. A rollout trip means flame left the burner area, which can indicate a blockage, incorrect gas pressure or a cracked heat exchanger.
Why do I need to read the error code before resetting the furnace?
On many control boards, a power reset clears the stored fault code, removing the most useful clue to what went wrong.
This article is general information for trained technicians. Gas and electrical work is hazardous. Follow manufacturer instructions, local codes and your employer’s procedures.